EIP Protocol

PLX3x Series

User Manual

Ethernet and Serial Gateways

Page 54 of 218

ProSoft Technology, Inc.

September 17, 2014

5.2

EIP Configuration

5.2.1 EIP Class 3 Server Connection

The EIP Class 3 Server Connection is used when the gateway is acting as a
server (slave) device responding to message instructions initiated from a Client
(Master) device such as an HMI, DCS, or PLC5.

Configuring EIP Class 3 Server Connections in PCB

The PLX3x Server connection file size is user selectable for 100 or 1000
integers. If a value of 100 is selected valid registers will be from N10:0 to N10:99.
If a value of 1000 is selected valid registers will be from N10:0 to N10:999.

Accessing the Gateway’s Internal Memory

Data Type

Tag Name

Length of Each Element in
CIP Message

Array Range for 4000
Element Database

BOOL

BOOLData[ ]

1

0 to 63999

Bit Array

BITAData[ ]

4

0 to 1999

SINT

SINTData[ ]

1

0 to 7999

INT

INT_Data[ ]

2

0 to 3999

DINT

DINTData[ ]

4

0 to 1999

REAL

REALData[ ]

4

0 to 1999

The following tables define the relationship of the gateway

’s internal database to

the addresses required in the MSG instructions:

MSG Instruction Type - CIP

Database
Address

CIP Integer

CIP Boolean

CIP Bit Array

CIP Byte

CIP DINT

CIP Real

0

Int_data[0]

BoolData[0]

BitAData[0]

SIntData[0]

DIntData[0]

RealData[0]

999

Int_data[999]

BoolData[15984]

SIntData[1998]

1000

Int_data[1000]

BoolData[16000]

BitAData[500]

SIntData[2000]

DIntData[500]

RealData[500]

1999

Int_data[1999]

BoolData[31984]

SIntData[3998]

2000

Int_data[2000]

BoolData[32000]

BitAData[1000]

SIntData[4000]

DIntData[1000] RealData[1000]

2999

Int_data[2999]

BoolData[47984]

SIntData[5998]

3000

Int_data[3000]

BoolData[48000]

BitAData[1500]

SIntData[6000]

DIntData[1500] RealData[1500]

3999

Int_data[3999]

BoolData[63999]

SIntData[9998]