7.3

MBS Diagnostics

7.3.1 PCB Diagnostics

The best way to troubleshoot the MBS driver is to use ProSoft Configuration
Builder to access the diagnostic capabilities of the gateway through the Ethernet
debug port. For instructions on how to access Diagnostics, see

Using

Diagnostics in ProSoft Configuration Builder

(page 36).

7.3.2 MBS Status Data in Upper Memory

Each Modbus port has an associated status data area located in the

gateway’s

upper memory. The Data Map functionality of the gateway can be used to map
this data into the normal user data range of the gateway

’s database. See

Using

the CommonNet Data Map

(page 25).

General Modbus Error and Status Data

The following table lists the starting addresses in upper memory where general
error and status data for each Modbus Master or slave port can be found.

Modbus Port

Starting Address

1

4400

2*

4800

3*

5200

4*

5600

*Status data for Ports 2 through 4 is only present in 4-port MBS gateways.

Note: None of the addresses are available in the Modbus address range. In order for them to be
accessed via a Modbus request, they must be moved into the 0 to 3999 address range. See

Using

the CommonNet Data Map

(page 25).

The status data area is initialized with zeros whenever the gateway is restarted.
This occurs during a cold-start (power-on), reset (reset push-button pressed) or a
warm-boot operation (commanded from a debug screen or after downloading a
new configuration).