4. Next add a New Module under the Generic EtherNet Bridge and add a

CIP-Connection. Here the parameters for the I/O connection are
specified. The input and output sizes need to match the input and output
sizes configured in PCB. The Address field value represents the
connection number in PCB. By default all of the connections have 248
Input words, 248 Output words, and 0 Configuration words. The Comm
format should be set to Data type INT, and the Assembly instances
should be "1" for input, "2" for output, and "4" for configuration.

5. A CIP Connection will need to be added and configured for each I/O

connection.

Configuring EIP Class 1 Connections in PCB

There are four configurable parameters for each I/O connection in PCB.

Parameter

Value Range

Description

Input Data
Address

0-3999

This parameter specifies the starting address within the
gateway

’s virtual database for data transferred from the

PLC to the module

Input Size

0-248

This parameter specifies the number of Integers being
transferred to the PLC's input image (248 integers max)

Output Data
Address

0-3999

This parameter specifies the starting address within the
gateway

’s virtual database for data transferred from the

module to the PLC

Output Size

0-248

This parameter specifies the number of integers being
transferred to the PLC's output image (248 integers max)