SIE Protocol

PLX3x Series

User Manual

Ethernet and Serial Gateways

Page 178 of 218

ProSoft Technology, Inc.

September 17, 2014

If DB1.DBD0 is used as the first address in the Siemens processor, the next
double word address that can be used without overwriting the data would be
DB1.DBD4.

All of the above share the same memory locations in the processor.

Note: Incorrect memory location addressing can cause the data to be overwritten.

Below is a graphical representation o

f the addressing of the processor’s memory

locations.

DB1.DBD1

DB1.DBW0

DB1.DBW1

DB1.DBW2

DB1.DBW3

2#0000_0110 2#0000_0000 2#0110_0001 2#0011_0110 2#1100_0110

DB1.DBB0DB1.DBB1

DB1.DBB2 DB1.DBB3 DB1.DBB4

DB1.DBD0

Example:

Sending an integer value of 11733 from gateway register 1000 to a Siemens S7-
300 processor demonstrates the addressing scheme in the Siemens S7-300
processor: