beautypg.com

ProSoft Technology PLX31-EIP-SIE User Manual

Page 133

background image

PLX3x Series

MBS Protocol

Ethernet and Serial Gateways

User Manual

ProSoft Technology, Inc.

Page 133 of 218

September 17, 2014

Port 1 General Modbus Error and Status Layout
The addresses listed are for Port 1only; but the format is the same for each port.
The start address for each port is given in the previous section.

Example Internal
Database Address

Offset

Description

4400

0

Number of Command Requests

4401

1

Number of Command Responses

4402

2

Number of Command Errors

4403

3

Number of Requests

4404

4

Number of Responses

4405

5

Number of Errors Sent

4406

6

Number of Errors Received

4407

7

Configuration Error Code

4408

8

Current Error/Index

4409

9

Last Error/Index

Slave Port: General Port STATE and COMM STATE Status

Note: There are two additional port status parameters that are not available from the General
Modbus Error and Status Data area. The status values, Port STATE and Port COMM STATE

(circled in red), can be found only in the PCB diagnostic menus under Comm Status for a port as

shown in the following graphic.