Mbtcp client command list error data – ProSoft Technology PLX31-EIP-SIE User Manual
Page 107
PLX3x Series
MBTCP Protocol
Ethernet and Serial Gateways
User Manual
ProSoft Technology, Inc.
Page 107 of 218
September 17, 2014
MBTCP Client Command List Error Data
A status/error code is held in upper memory for each command in each MBTCP
Client
’s command list.
The following table lists the addresses in upper memory that hold command list
error data for each MBTCP Client.
Client
Address Range
0
15510 through 15525
1
15536 through 15551
2
15562 through 15577
.
.
.
.
8
15718 through 15733
9
15744 through 15759
The first word in each
Client’s command list error data area contains the
status/error code for the first command in the Client
’s Command List. Each
successive word in the Command Error List is associated with the next command
in the Client Command List. Therefore, the number of valid error values is
dependent upon the number of commands defined.
The structure of the command list error data area (which is the same for all
Clients) is displayed in the following table.
Offset
Description
0
Command #1 Error Code
1
Command #2 Error Code
2
Command #3 Error Code
3
Command #4 Error Code
4
Command #5 Error Code
.
.
.
.
.
.
13
Command #14 Error Code
14
Command #15 Error Code
15
Command #16 Error Code
A non-zero error code for a command indicates an error. To interpret the
status/error codes, refer to
(page 108).