As the commands in the Client Command List are polled and executed, an error
codeis maintained in the gateway for each command. The current error value for
each command is displayed in the Command List Errors section of each Client’s
status data area. There is one register for each of the 16 commands in the
command list. An error code of 0 means no error is currently detected for the
specified command.
The following tables list the various error codes that may be displayed and their
descriptions.

9.3.2 SIE Error Codes

Module Communication Error Codes

Decimal

Hex

Description

1

0x0001

No data from I/O module

3

0x0003

The desired item is not available in the PLC (200 family)

5

0x0005

The desired address is beyond limit for this PLC

6

0x0006

The CPU does not support reading a bit block of length<>1

7

0x0007

Write data size error

10

0x000a

The desired item is not available in the PLC

-123

0xff85

Cannot evaluate the received PDU

-124

0xff84

The PLC returned a packet with no result data

-125

0xff83

The PLC returned an error code not understood by this library

-126

0xff82

This result contains no data

-127

0xff81

Cannot work with an undefined result set

-128

0xff80

Unexpected function code in answer";

-129

0xff7f

PLC responds with an unknown data type

-1024

0xfc00

Short packet from PLC

-1025

0xfbff

Timeout when waiting for PLC response

-32767

0x8001

Not allowed in current operating status

-32511

0x8101

Hardware fault

-32509

0x8103

Object access not allowed

-32508

0x8104

Context is not supported. Step7 says: Function not implemented or error in
telegram

-32507

0x8105

Invalid address

-32506

0x8106

Data type not supported