Start here, System requirements, Ge 9) – ProSoft Technology MVI69-101S User Manual
Page 9: 1 start here

Start Here
MVI69-101S ♦ CompactLogix or MicroLogix Platform
IEC 60870-5-101 Slave Communication Module
ProSoft Technology, Inc.
Page 9 of 149
March 16, 2009
1 Start
Here
In This Chapter
System Requirements .............................................................................9
Package Contents ................................................................................. 10
Install ProSoft Configuration Builder Software....................................... 10
Setting Jumpers .................................................................................... 12
Install the Module in the Rack ............................................................... 12
Connect your PC to the Processor ........................................................ 16
Download the Sample Program to the Processor.................................. 16
Connect your PC to the Module ............................................................ 19
Installing the MVI69-101S module requires a reasonable working knowledge of
the Rockwell Automation hardware, the MVI69-101S Module and the application
in which they will be used.
Caution: It is important that those responsible for implementation can complete the
application without exposing personnel, or equipment, to unsafe or inappropriate working
conditions. Safety, quality and experience are key factors in a successful installation.
1.1 System
Requirements
The MVI69-101S module requires the following minimum hardware and software
components:
Rockwell Automation CompactLogix or MicroLogix processor, with
compatible power supply and one free slot in the rack, for the MVI69-101S
module. The module requires 800mA of available power.
Important: The MVI69-101S module has a power supply distance rating of 2 (L43 and L45
installations on first 2 slots of 1769 bus).
Important: For 1769-L23x processors, please make note of the following limitations.
1769-L23-QBFC1B = 800mA at 5Vdc (1 MVI69-101S will use all 800mA of available power.
No other modules can be used with an MVI69 module connected to this processor).
1769-L23E-QB1B = 1000mA at 5Vdc (1 MVI69-101S will use 800mA of available power. One
other module can be used on this rack provided it consumes less than 200mA at 5Vdc.
1769-L23E-QBFC1B = 450mA at 5Vdc (no MVI69 module can be used with this processor)
Rockwell Automation RSLogix 5000 (CompactLogix) or RSLogix 500
(MicroLogix) programming software
Rockwell Automation RSLinx communication software