Monitor data transfer – ProSoft Technology MVI69-101S User Manual
Page 100

MVI69-101S ♦ CompactLogix or MicroLogix Platform
Reference
IEC 60870-5-101 Slave Communication Module
Page 100 of 149
ProSoft Technology, Inc.
March 16, 2009
Monitor Data Transfer
In unbalanced mode the polling procedure is initiated from the master unit
through Class 1 and Class 2 requests. In general, ASDUs containing the causes
of transmission periodic/cyclic are assigned to be transmitted with class 2
requests and all time tagged or spontaneously transmitted ASDUs are assigned
to be transmitted through class 1 requests. Other ASDUs with other causes of
transmission of low priority such as background scan may also be assigned to
class 2 requests.
Typically, you should properly configure the group code for each monitor point to
define how the master will poll for the point. The group codes are defined as
follows:
The Group parameter is defined as follows:
Group Code
Description
0x00000001
Interrogated by general interrogation (station or global)
0x00000002
Interrogated by group 1 interrogation
0x00000004
Interrogated by group 2 interrogation
0x00000008
Interrogated by group 3 interrogation
0x00000010
Interrogated by group 4 interrogation
0x00000020
Interrogated by group 5 interrogation
0x00000040
Interrogated by group 6 interrogation
0x00000080
Interrogated by group 7 interrogation
0x00000100
Interrogated by group 8 interrogation
0x00000200
Interrogated by group 9 interrogation
0x00000400
Interrogated by group 10 interrogation
0x00000800
Interrogated by group 11 interrogation
0x00001000
Interrogated by group 12 interrogation
0x00002000
Interrogated by group 13 interrogation
0x00004000
Interrogated by group 14 interrogation
0x00008000
Interrogated by group 15 interrogation
0x00010000
Interrogated by group 16 interrogation
0x00020000
Interrogated by general counter request
0x00040000
Interrogated by group 1 counter request
0x00080000
Interrogated by group 2 counter request
0x00100000
Interrogated by group 3 counter request
0x00200000
Interrogated by group 4 counter request
0x40000000
Disable event scanning of this point
0x80000000
Periodic/cyclic data returned from unit
The module will periodically send all points configured for periodic/cyclic poll
(0x80000000) at every x milliseconds, where x is configured with the following
parameter:
Cyclic data transmission: 20000 #Numb of milliseconds between cyclic
#updates