ProSoft Technology MVI69-101S User Manual
Page 52

MVI69-101S ♦ CompactLogix or MicroLogix Platform
Ladder Logic
IEC 60870-5-101 Slave Communication Module
Page 52 of 149
ProSoft Technology, Inc.
March 16, 2009
Block Transfer Size = 120
Field Recommended
Value
Input Assembly Instance
101
Input Size
122
Output Assembly Instance
100
Output Size
121
Configuration Assembly Instance
102
Configuration Size
0
Block Transfer Size = 240
Field Recommended
Value
Type
1769-MODULE Generic 1769 Module
Parent Local
Name MVI69
Description
MVI69 Application Module
Comm Format
Data - INT
Slot
The slot number in the rack where the module is installed
Input Assembly Instance
101
Input Size
242
Output Assembly Instance
100
Output Size
241
Configuration Assembly Instance
102
Configuration Size
0
5 Click Next to continue.
6 Select the Request Packet Interval value for scanning the I/O on the module.
This value represents the minimum frequency the module will handle
scheduled events. This value should not be set to less than 1 millisecond.
Values between 1 and 10 milliseconds should work with most applications.