Mvi69101s_control, Mvi69101s_eventblock, Mvi69101s_event – ProSoft Technology MVI69-101S User Manual
Page 47: Mvi69101s_clock

Ladder Logic
MVI69-101S ♦ CompactLogix or MicroLogix Platform
IEC 60870-5-101 Slave Communication Module
ProSoft Technology, Inc.
Page 47 of 149
March 16, 2009
3.1.2 MVI69101S_CONTROL
The CONTROL tag contains special tags for special tasks to be requested to the
module.
Name Data
Type
Description
Event
MVI69101S_EventBlock
Block 9958: Event message
SetTime MVI69101S_Clock
Block 9971: Writes the clock data to
the module
GetTime MVI69101S_Clock
Block 9970: Reads the clock data from
the module
MVI69101S_EventBlock
Name Data
Type
Description
Activate BOOL
Set this bit to 1 to activate event block
9958 to send events to the module
EventCount INT
Number of events to be sent at this
block (between 1 and 3)
Event MVI69101S_Event[3]
MVI69101S_Event
The Event tag describes the format of each event to be transferred from the
processor to the module.
Name Data
Type
Description
DBIndex
INT
Index of the point in configuration file
ASDU INT
1=SP, 3=DP, 5=STEP,9=NORM,
11=SCALED, 15=INTEGRATED
Qualifier INT
Qualifier
Code
Year
INT
Year of timestamp
Month
INT
Month of timestamp
Day INT
Day
of
timestamp
Hour
INT
Hour of timestamp
Minute
INT
Minute of timestamp
Seconds_Milliseconds INT
For example, a value of 15742 means
15secs and 742 milliseconds
Data INT[6]
Data associated to event: data size will
depend on point type - check
documentation
MVI69101S_Clock
The Clock tag contains the format to read and write the module's date and time
information.
Name Data
Type
Description
Activate BOOL
Year INT
Month INT