Iv fail count, Event scan delay, Scan events – ProSoft Technology MVI69-101S User Manual
Page 32: Time type, Use balanced mode

MVI69-101S ♦ CompactLogix or MicroLogix Platform
Configuring the MVI69-101S Module
IEC 60870-5-101 Slave Communication Module
Page 32 of 149
ProSoft Technology, Inc.
March 16, 2009
2.3.21 IV Fail Count
0 to disable
This feature allows the application to set the invalid (IV) quality bit of the protocol
for all the monitored ASDU types supported. If you enable this feature, the
processor can determine the individual IV quality bit status of each point you
configured.
To disable this feature, set the IV Fail Count parameter to 0. If used, the Cyclic
Set IV Time parameter must be at least 3 times larger than the IV Check Delay
Time.
2.3.22 Event Scan Delay
1 to 65535
0 to disable
If set to 0, the feature will be disabled and the module will not generate any
events. If set from 1 to 65535, the parameter represents the number of
milliseconds between event scanning. This parameter defines how often the
program will scan for new events in the databases.
2.3.23 Scan Events
Scan for Events
No Scanning
Determines if events of this point type will be generated by the module. If "No
Scanning", then events will not be generated. If "Scan for events", events will be
scanned and generated on change.
2.3.24 Time Type
None, CP24 or CP56
This parameter defines the time format used with data events. 0=None, 1=CP24
and 2=CP56 time formats.
2.3.25 Use Balanced Mode
Yes or No
This parameter specifies if the port will use balanced mode. If balanced mode is
used, only one controlled station will be permitted on the port. If unbalanced
mode is used, multiple controlled stations can be used on a port. Select Yes to
use balanced mode and No to use unbalanced mode.