ProSoft Technology MVI69-101S User Manual
Page 137

Reference MVI69-101S
♦ CompactLogix or MicroLogix Platform
IEC 60870-5-101 Slave Communication Module
ProSoft Technology, Inc.
Page 137 of 149
March 16, 2009
Transmission of Integrated totals
(Station- or object-specific parameter)
⌧ Counter
request
⌧
General request counter
⌧
Counter freeze without reset
⌧
Request counter group 1
Counter freeze with reset
⌧
Request counter group 2
Counter
reset
⌧
Request counter group 3
⌧
Request counter group 4
Addresses per group have to be defined
Parameter loading
(Object-specific parameter)
⌧ Threshold
value
Smoothing
factor
⌧
Low limit for transmission of measured value
⌧
High limit for transmission of measured value
Parameter activation
(Object-specific parameter)
Act/deact of persistent cyclic or periodic transmission of the addressed
object
File transfer
(Station-specific parameter)
File transfer in monitor direction
File transfer in control direction
Note 1: Delay acquisition command supports Load Delay only.
Note 2: C_SE_ACTTERM may be enabled or disabled at time of installation.
Note 3: The ASDU length can be configured by the user (between 25 and 252).
Note 4: Only applies to C_SC_NA_1 and C_DC_NA_1 commands.
Note 5: The low limits and high limit values are calculated based on the
Deadband values as follows:
Low Limit: Last reported event value - threshold
High Limit: Last reported event value + threshold