Controlling the generation of events, General (all points), Data type level – ProSoft Technology MVI69-101S User Manual
Page 115

Reference MVI69-101S
♦ CompactLogix or MicroLogix Platform
IEC 60870-5-101 Slave Communication Module
ProSoft Technology, Inc.
Page 115 of 149
March 16, 2009
So, in order to send change the deadband for the M_ME_NA point 400, the
master would send a command type 110 to point 2400:
Controlling the Generation of Events
Some applications may require that only some points should generate
events.Other applications may require that all configured points should generate
events.
The module offers considerable flexibility for event control. You can control how
events will be generated at 3 different levels:
1 General (All Points)
2 Data Type Level
3 Point Level
General (All Points)
You can control how frequently the module will scan the database for events
using the following configuration parameter:
Event Scan delay : 1 #MSec between event scanning (0-65535)
#0=Disable
If this parameter is set to 0, the module will not generate events for any points. A
non-zero value will configure how frequently the module will scan for events in
the database.
Data Type Level
You can configure whether a data type should generate events. Each data type
has a configuration parameter to control the generation of events:
M_SP_NA Scan Events : 1 #0=No scanning, 1=scan for events
M_DP_NA Scan Events : 0 #0=No scanning, 1=scan for events
M_ST_NA Scan Events : 0 #0=No scanning, 1=scan for events
M_ME_NA Scan Events : 0 #0=No scanning, 1=scan for events
M_ME_NB Scan Events : 0 #0=No scanning, 1=scan for events
M_ME_NC Scan Events : 0 #0=No scanning, 1=scan for events
In the example above, only the M_SP_NA points would generate events.