Common address of asdu, Common address of asdu len, Inform. object address len – ProSoft Technology MVI69-101S User Manual
Page 29: Select/operate timeout, Cyclic data transmission, Use actterm with setpoint

Configuring the MVI69-101S Module
MVI69-101S ♦ CompactLogix or MicroLogix Platform
IEC 60870-5-101 Slave Communication Module
ProSoft Technology, Inc.
Page 29 of 149
March 16, 2009
2.3.5 Common address of ASDU
Common address of ASDU : 1 #Range 0 to 65535
This parameter specifies the common address of the ASDU (section address) for
access to data in the module. There is only one value entered for access to all
data in the module.
2.3.6 Common address of ASDU Len
1 or 2
This parameter specifies the number of octets used for the common address of
ASDU. This parameter must be set the same for all devices on the network.
2.3.7 Inform. Object address Len
1, 2 or 3
This parameter sets the number of octets used to specify the address for an
information object in each sector for this session.
2.3.8 Select/Operate
Timeout
Select/Operate Timeout : 2000 #Milliseconds before select timeout
This parameter sets the number of milliseconds after a select command is
received in which to wait for a valid execute command. If the parameter is set to
0, the feature will be disabled.
2.3.9 Cyclic Data Transmission
Cyclic data transmission : 60000 #Numb of milliseconds between cyclic
#updates
This parameter defines the number of milliseconds between cyclic updates. If the
parameter is set to 0, cyclic data reporting will be disabled.
2.3.10 Use ACTTERM with Setpoint
Use ACCTERM with setpoint : 1 #1=Yes, 0=No aCTCON is last response
#to cmd
This parameter determines if an ACCTERM will be sent. If the parameter is set to
Y, then setpoint commands will issue an ACCTERM when the command is
complete. If the parameter is set to N, aCTCON is the last response to a setpoint
command.