M_st_na, M_me_na and m_me_nb – ProSoft Technology MVI69-101S User Manual
Page 106

MVI69-101S ♦ CompactLogix or MicroLogix Platform
Reference
IEC 60870-5-101 Slave Communication Module
Page 106 of 149
ProSoft Technology, Inc.
March 16, 2009
These points would be used as follows:
Inf. Object Address
Module Database Address
100
Bit 0 of word 100
101
Bit 1 of word 100
102
Bit 2 of word 100
The monitored double-point uses two bits with bit-addressing. It typically
represents the ON/OFF states where:
01 = OFF
10 = ON
M_ST_NA
The monitored step-point uses one byte with byte-addressing.
For example, if you configured the following points:
# Point # DB Address Group(s) IV DB Bit
# ------- ---------- -------- -------------
START
300 40 80000000 0
301 60 00000200 0
302 81 00000400 0
END
These points would be used as follows:
Inf. Object Address
Module Database Address
300
Low Byte of word 20
301
Low Byte of word 30
302
High Byte of word 40
M_ME_NA and M_ME_NB
The monitored measured normalized and measured scaled points occupy one
word with word-addressing.
For example, if you configured the following points:
# Default
# Point # DB Address Group(s) Deadband IV DB Bit
# ------- ---------- -------- -------- ---------
START
400 10 80000000 0 0
401 12 00000200 0 0
402 18 00000400 0 0
END
These points would be used as follows:
Inf. Object Address
MVI69-101S Module Database Address
400 Word
10
401 Word
12
402 Word
18
The monitored measured normalized points use a data representation defined by
the protocol specification, where each bit represents a value as follows: