B.10 SOURce:CURRent COMMAND

SOUR:CURR

Syntax:

Short Form: SOUR:CURR

Long Form: SOURce:CURRent

Description:

Sets the output current value. Maximum output current is rated current; minimum current is
zero.

Argument:

is a value in the range from 0 to rated current of unit. Rated voltage and current are defined
by model (e.g., for KLN 6-100, rated voltage is 6V, rated current is 100A).

Example:

SOURce:CURRent 25 sets output current value to 25A.

B.11 SOURce:CURRent?

QUERY

SOUR:CURR?

Syntax:

Short Form: SOUR:CURR?

Long Form: SOURce:CURRent?

Description:

Indicates programmed output current (in amperes).

Return Format:
Example:

SOURce:CURRent? returns 2.50000E+01 to indicate output current is programmed to 25A.

B.12 SOURce:CURRent:PROTection:LEVel COMMAND

SOUR:CURR:PROT:LEV

Syntax:

Short Form: SOUR:VOLT:PROT:LEV
Long Form: SOURce:CURRent:PROTection:LEVel

Argument:

is a value in the range from 10% to 110% of rated current.
MIN is the value programmed for output current (SOUR:CURR)
MAX is 110% of rated current of unit

Description:

Sets the overcurrent protection (OCP) value (in amperes). OCP values set using this com-
mand are in effect once the unit is returned to local operation. Maximum value is 110% of rated
voltage. MIN sets OCP to be the same as the value programmed for output current. *RST sets
SOUR:CURR:PROT:LEV to maximum value.

Example:

SOURce:CURRent:PROtection:LEVel 27.5 sets the overcurrent protection level to 27.5A. This is
the maximum value if the unit is a 30V, 25A model. SOUR:CURR:PROT:LEV MIN sets the over-
current protection level to be the same as the programmed value of output current (SOUR:CURR).

B.13 SOURce:CURRent:PROTection:LEVel?

QUERY

SOUR:CURR:PROT:LEV?

Syntax:

Short Form: SOUR:CURR:PROT:LEV? Long Form: SOURce:CURRent:PROtection:LEVel?

Description:

Indicates programmed overcurrent protection (OCP) level for output current (in amperes).

Return Format:
Example:

SOURce:CURRent:PROtection:LEVel? returns 2.75000E+01 to indicate overcurrent protection
level is programmed to 27.5A.

B.14 SOURce:LIST:DTIMe COMMAND

SOUR:LIST:DTIM

Syntax:

Short Form: SOUR:LIST:DTIM Long Form: SOURce:LIST:DTIMe

Description:

Sets the output ramp-down time.

Argument:

is a value in the range from 0.0 to 9.9 seconds.

Example:

SOURce:LIST:DTIMe 3.0 programs the output ramp-down time to 3.0 seconds.

B.15 SOURce:LIST:DTIMe?

QUERY

SOUR:LIST:DTIM?

Syntax:

Short Form: SOUR:LIST:DTIM?

Long Form: SOURce:LIST:DTIMe?

Description:

Indicates (in seconds) how long output voltage takes to reach zero from programmed
value.

Return Format:
Example:

SOURce:LIST:DTIMe? returns 3.00000+E00 to indicate ramp-down time is 3.0 seconds.