2-14

KLN 750W 032614

FIGURE 2-12. OPTIONAL SERIES CONNECTION KIT

2.8.2

PARALLEL CONNECTIONS

Up to five identical KLN 750W units (one master and up to four slaves) can be operated in par-
allel to increase the output current. Output current of the parallel combination = number of units
in parallel x output current of a single unit.

1. See Figure 2-13 for parallel connections without remote sensing and Figure 2-14 for parallel

connections with remote sensing. See PAR. 2.5.5 for guideline regarding load connections.
See PAR. 3.4.3 for operating units connected in parallel.

CAUTION: OBSERVE CORRECT POLARITY FOR ALL CONNECTIONS.

2. See Figure 2-15 for Programming Control Port Connections for parallel operation.

FIGURE 2-13. PARALLEL CONNECTIONS WITHOUT REMOTE SENSING

NOTE:
Adding local sensing wires
from + to +S and from – to –S
on both the Master and Slave
will make the front panel volt-
age reading slightly more
accurate (~10mV).