beautypg.com

Precision Digital PD6830 User Manual

Page 8

background image

PD6830 Pulse Input Rate/Totalizer Instruction

Manual

8

PASSWORD MENU
OPTIONS

Three programmable password selections can be used for the
following: restrict modification of settings, prevent resetting the
total or grand total without the password, or permanently lock out
the ability to change or reset the grand total or any grand total
related settings (making a non-resettable grand total).
Pass: Restricts modifications of programmed settings to require
re-entering the password to make changes.
Pass T: Restricts the reset of total to require re-entering the
password. Disables the manual mode reset contact.
Pass GT: Restricts the reset of grand total to Require re-entering
the password. May enable a non-resettable grand total and
permanent lockout of grand total-related settings with a specific
password.

POWER OPTIONS

9-30 VDC Powered, 2.2 W max

4-20 mA Output Powered, 30 VDC max

Battery Power

9-30 VDC Powered with Battery Backup

4-20 mA Output Powered with Battery Backup

BATTERY

3.6 V Primary Lithium (Li-SOCl

2

), non-rechargeable

Model PDABAT36C

Expected Service Life & Recommended Replacement Interval

Operating Condition

Estimated

Service

Life

Suggested

Replacement

Interval

Open collector outputs off,
SafeTouch buttons off, minimal
backlight use

7.5 years

5.5 years

<100 Hz open collector outputs,
minimal SafeTouch button or
backlight use

5.5 years

4 years

<2 kHz open collector outputs,
minimal SafeTouch button or
backlight use

2.5 years

2 years

<5 kHz open collector outputs,
minimal SafeTouch button or
backlight use

1.3 years

1 year

Backup power only

N/A

10 years

DATA LOGGING

Up to 1024 records, recorded 4/day at specific times or at
defined time intervals. Record contains date, time, rate, total,
grand total, and log number.