20 ma transmitter output, Open collector outputs – Precision Digital PD6830 User Manual

Page 13

background image

PD6830 Pulse Input Rate/Totalizer Instruction

Manual

13

4-20 mA Transmitter Output

OUTPUT SOURCE

Rate/process, total, grand total, or disabled

SCALING RANGE

4.000 to 20.000 mA for any display range.

DISABLE

If disabled, the output will output 3.2 mA

CALIBRATION

Factory Calibrated: 0.0 to 1000.0 = 4-20 mA output

UNDERRANGE

Output Underrange: 3.8 mA

OVERRANGE

Display Overrange: 20.5 mA

Output Overrange: 20.5 mA

ACCURACY

± 0.05% span ± 0.004 mA

TEMPERATURE
DRIFT

0.08 µA/

C max from -40 to 75C ambient,

EXTERNAL LOOP
POWER SUPPLY

30 VDC maximum

OUTPUT LOOP RE-
SISTANCE

Power supply

Minimum

Maximum

24 VDC

10

 750

30 VDC

100

 1100

Note: loop-powered backlight subtracts 150

from maxi-

mum resistance figures above.

Open Collector Outputs

OUTPUT
ASSIGNMENT

Two open collector pulse outputs Out 1 and Out 2.
Individually programmable for rate, total, or grand total alarms;
rate, total, or grand total pulse outputs; or retransmitting of
pulse inputs; constant timed pulse output; quadrature outputs
(requires Out 1 and Out 2); or off.

RATING

Isolated open collector, off: 24 VDC max, on: <1 V @ 150 mA
max

ALARM OUTPUT

Assign to rate for high or low alarm trip point.
Assign to total or grand total for total or grand total alarms.

ALARM
DEADBAND

0-100% FS, user selectable

ALARM
ACKNOWLEDGE

Front panel ENTER button resets output and screen indication.