PD6830 Pulse Input Rate/Totalizer Instruction

Manual

73

Manual or Automatic Grand Total Reset Function (GtrST)

For manual reset, select T RESET  Gtrst  man and then select whether manual
reset will be enabled (Enabl) or disabled (dsabl) using the Up arrow key. Press the
Enter

button to accept. Disabling reset will avoid inadvertent resets of the total via

the front reset button.
For automatic reset, select T RESET  Gtrst  Auto T DELAY and enter reset
delay time in seconds. Once the grand alarm output grand total set point is reached,
the meter waits for a programmed amount of time (T DELAY) and then resets the
grand total to zero.
For timed reset, select T RESET  t rst  Time T RESET and enter the time of
day at which the total should be reset. The total value will be reset every day at the
specified time.
Press the Enter button, at any time, to accept a setting; otherwise press the Menu
button to exit without saving changes.

Grand Total Alarm Time

The T DELAY parameter is used by the NPN open collector outputs when they are
programmed as grand total alarms. If grand total reset (Gtrst) is programmed to
Auto

,the time delay (T DELAY) is the length of the associated Out 1 or Out 2 grand

total alarm prior to the grand total being reset to 0.
For information on programming the NPN open collector pulse outputs as grand total
alarms, see Alarm Output programming on page 62.
Press the Enter button, at any time, to accept a setting; otherwise press the Menu
button to exit without saving changes.