PD6830 Pulse Input Rate/Totalizer Instruction

Manual

14

PULSE OUTPUT K-
FACTOR (COUNT)

K-factor (couNT) programmable from 0.000001 to 9999999.
Rate pulses are generated as a scaled output of the rate input
with one output pulse per K-factor (count) number of input
pulses. Total and grand total pulses are generated for every
total or grand total increment selected. (e.g. K-factor value of
100 will generate one pulse every time the total is incremented
by 100 units)
Rate retransmission pulses one to one for input pulses, up to
maximum output speed. K-factor is not used for retransmitting
outputs.

PULSE OUTPUT
PULSE WIDTH

Unless otherwise stated, pulses are 50% duty cycle for re-
quired frequency.
A pulse rate retransmit output will generate 100 to 130 μs
pulses at the falling edge of every input pulse.

PULSE OUTPUT
MAXIMUM
FREQUENCY

5 kHz, pulse width at 50% duty cycle.
If the programming of the outputs would exceed 5 kHz, the
meter will display pUlse OVERRNG

QUADRATURE
OUTPUT

Output set to quadrature will lag the other pulse output by 90°
(1/4 duty cycle) at output frequency. Minimum 1 Hz

TIMER OUTPUT

Programmable on and off time, repeating cycle. Minimum pe-
riod 0.1 second, maximum 100,000 seconds. Minimum pulse
time 0.01 second, maximum 10,000 seconds.

Serial Communications

PROTOCOL

2-Wire RS-485 Modbus® RTU

METER AD-
DRESS/SLAVE ID

1 - 247

BAUD RATE

1,200; 4,800; 9,600; 19,200; 38,400; 57,600;
or 115,200 bps

TRANSMIT TIME
DELAY

Programmable between 0 and 199 ms

PARITY/STOP BIT

Even, odd, none with 1 stop bit, or none with 2 stop bits

BYTE-TO-BYTE
TIMEOUT

Max of 1.5 character times or 750 μs

Note: Refer to Modbus Register Tables at www.predig.com for details.