To configure the meter for non-resettable grand total mode, enter the non-resettable 
grand total password below into the Pass GT parameter in the Password menu. 
The non-resettable grand total permanently locks the following setup menus and 
parameters from being changed: input selection, K-factor, K-factor units, grand total 
units, grand total conversion factor, grand total decimal point, scaling, calibration, 
grand total alarms, pulse input filter, and cutoff. 
 
 
Non-resettable grand total password: 50873 
 
Non-Resettable Grand Total Locked Menus & Parameters
Display Parameter/Menu
Action/Setting
Locked
Input
Input
All Input type selection menu parameters
GtotU
Grand total units
Set grand total units
GrtCF
Grand total con-
version factor 
Enter the Grand Total Conversion Factor 
menu 
Grtot 
DECIMAL
Grand total dec-
imal point 
Enter the grand total display decimal point
Factr
K-factor
All K-Factor menu parameters
sCalE
Scale
All Scale menu parameters
Cal
Calibrate
All Calibrate menu parameters
GTrST
Grand total reset
All the Grand Total Reset menu parameters
Pass GT
Password grand 
total 
Enter the grand total reset password
Grtot 
ALARM 
Grand total alarm
All grand total alarm output menu parameters
FILTER
Filter
Enter Filter parameter
CUTOFF
Low-flow cutoff
Enter Low-Flow Cutoff parameter
The above menus remain accessible; however the parameters listed above within the 
menus are locked and may not be changed. 
CAUTION
Locking the meter into a non-resettable grand total is not 
reversible. It is a permanent meter configuration. Doing so will 
permanently prevent most input parameters from being altered. 
This should be the last step after verifying all setup parameters. 