Precision Digital PD6830 User Manual
Page 76

PD6830 Pulse Input Rate/Totalizer
Instruction Manual
76
To configure the meter for non-resettable grand total mode, enter the non-resettable
grand total password below into the Pass GT parameter in the Password menu.
The non-resettable grand total permanently locks the following setup menus and
parameters from being changed: input selection, K-factor, K-factor units, grand total
units, grand total conversion factor, grand total decimal point, scaling, calibration,
grand total alarms, pulse input filter, and cutoff.
Non-resettable grand total password: 50873
Non-Resettable Grand Total Locked Menus & Parameters
Display Parameter/Menu
Action/Setting
Locked
Input
Input
All Input type selection menu parameters
GtotU
Grand total units
Set grand total units
GrtCF
Grand total con-
version factor
Enter the Grand Total Conversion Factor
menu
Grtot
DECIMAL
Grand total dec-
imal point
Enter the grand total display decimal point
Factr
K-factor
All K-Factor menu parameters
sCalE
Scale
All Scale menu parameters
Cal
Calibrate
All Calibrate menu parameters
GTrST
Grand total reset
All the Grand Total Reset menu parameters
Pass GT
Password grand
total
Enter the grand total reset password
Grtot
ALARM
Grand total alarm
All grand total alarm output menu parameters
FILTER
Filter
Enter Filter parameter
CUTOFF
Low-flow cutoff
Enter Low-Flow Cutoff parameter
The above menus remain accessible; however the parameters listed above within the
menus are locked and may not be changed.
CAUTION
Locking the meter into a non-resettable grand total is not
reversible. It is a permanent meter configuration. Doing so will
permanently prevent most input parameters from being altered.
This should be the last step after verifying all setup parameters.