M a i n t e n a n c e / T r o u b l e s h o o t i n g

Page 50

Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN

Status

Display

Explanation

Action

By

OS 64

Measured values

Output current limiting: The AC cur-

rent is limited once the specifi ed maxi-
mum value has been reached.

-

-

FS

67

Fault

power section 1

There is a fault in the power section.

 Notify your author-

ised electrician.

E

FS

70

Fan 1 error

Fan 1 is indicating a malfunction.

 Replace defective

fan (see section 9.4
on page 42).

B

FS

71

Fan 2 error

Fan 2 is indicating a malfunction.

B

FS

72

Fan 3 error

Fan 3 is indicating a malfunction.

B

FS

73

Standalone grid

err.

Standalone mode was detected.

-

-

OS 74

External idle

power require-
ment

The grid operator limits the feed-in

power of the inverter.

-

-

Table 6:

Operating states and fault messages on the display

BS = operating status, FS = fault status;

B = Action of the operator

E = The indicated work must only be carried out by an authorised electrician.

K = The indicated work must be carried out only by a service employee of KACO new energy GmbH.