KACO Powador 16.0 TR3 User Manual
Page 49
M a i n t e n a n c e / T r o u b l e s h o o t i n g
Page 50
Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN
Status
Display
Explanation
Action
By
OS 64
Measured values
Output current limiting: The AC cur-
rent is limited once the specifi ed maxi-
mum value has been reached.
-
-
FS
67
Fault
power section 1
There is a fault in the power section.
Notify your author-
ised electrician.
E
FS
70
Fan 1 error
Fan 1 is indicating a malfunction.
Replace defective
fan (see section 9.4
on page 42).
B
FS
71
Fan 2 error
Fan 2 is indicating a malfunction.
B
FS
72
Fan 3 error
Fan 3 is indicating a malfunction.
B
FS
73
Standalone grid
err.
Standalone mode was detected.
-
-
OS 74
External idle
power require-
ment
The grid operator limits the feed-in
power of the inverter.
-
-
Table 6:
Operating states and fault messages on the display
BS = operating status, FS = fault status;
B = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must be carried out only by a service employee of KACO new energy GmbH.