3 country-specifi c parameter settings – KACO Powador 16.0 TR3 User Manual
Page 14
T e c h n i c a l D a t a
Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN
Page 15
4.3 Country-specifi c parameter settings
Grid voltage
range
[V]
Grid voltage
according to
EN 50160
[V]
Standard
frequency
range
[Hz]
Switch-on time
after restart*
[s]
Restart time after
feed-in power that
is too low* [s]
Restart time
after fault*
[s]
DE
190 to 264
253
47.5 to 50.2
> 60
> 180
> 30
ES
196 to 254
-
49.0 to 51.0
> 180
> 180
> 180
IT
190 to 264
-
49.7 to 50.3
> 180
> 180
> 30
FR
190 to 264
253
49.5 to 50.5
> 60
> 180
> 30
CY
208 to 252
-
49.5 to 50.5
> 180
> 180
> 180
GR
190 to 264
-
49.5 to 50.5
> 180
> 180
> 180
KR
194 to 242
-
59.7 to 60.3
> 360
> 360
> 360
CZ
196 to 252
253
47.0 to 51.0
> 60
> 180
> 30
PT
196 to 264
253
47.0 to 51.0
> 60
> 180
> 30
BG
196 to 264
-
47.0 to 51.0
> 60
> 180
> 30
* approx. values
Table 3:
Country-specifi c parameter settings