Messages on the display/“Fault” LED

Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The minimum triggering
levels are determined by standards (e.g. VDE0126-1-1). The inverter must switch off if the permitted values are under-
shot or exceeded.

9.7.1

Display of status and fault messages

Display

Fault LED (red)

FS (fault status)

ON

Fault signal relay has switched.

Feed-in was ended due to a fault.

OS (operating status)

OFF

The fault signal relay deenergizes again.

The inverter feeds back into the grid again after a
country-specifi c time period.

On the display you can fi nd details regarding the fault or operating status or the data that was recorded through the
RS485 interface.

9.7.2

Status and fault signals

The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.

Status

Display

Explanation

Action

By

OS 1

Waiting for feed-

in

Self test: Grid parameters and genera-

tor voltage are being checked.

-

-

OS 2

Generator voltage

too low

Insuffi

cient generator voltage and

power,

status before the transition to night

shutdown

-

-

OS 7

Self-test

Checks the shutdown of the power

electronics as well as the line relay
before feed-in mode The self-test
consists of three successive individual
tests with the status 7, 75 and 8.

-

-

OS 75

Self-test

OS 8

Self-test

FS

10

Temperature in

unit too high

In case of overheating, the inverter

switches off . Possible causes:

Ambient temperature too high

Fans covered

Inverter defect

 Cool off the vicinity

of the inverter.

 Uncover the fans.

 Notify your author-

ised electrician.

B

B
E

Table 6:

Operating states and fault messages on the display

BS = operating status, FS = fault status;

B = Action of the operator

E = The indicated work must only be carried out by an authorised electrician.

K = The indicated work must be carried out only by a service employee of KACO new energy GmbH.