KACO Powador 16.0 TR3 User Manual
Page 47

M a i n t e n a n c e / T r o u b l e s h o o t i n g
Page 48
Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN
Status
Display
Explanation
Action
By
OS 11
Measured values
Power limitation: If the generator
power is too high, the inverter limits
itself to the maximum power (e.g. in
the midday hours if the generator has
been too largely dimensioned).
-
-
OS 29
Check ground
fault fuse
A ground fault was detected on the
DC side.
Check the PV gen-
erator
E
FS
30
Voltage
trans. fault
The current and voltage measure-
ments in the inverter are not plausible.
-
-
FS
32
Fault
Self-test
The internal grid separation relay test
has failed.
Notify your author-
ised electrician if the
fault occurs several
times.
E
FS
33
Fault
DC feed in
The DC feed-in has exceeded the
permitted value. This DC feed-in can
be adopted from the grid onto the
inverter so that no fault occurs.
Notify your author-
ised electrician if the
fault occurs several
times.
E
FS
34
Internal commu-
nication error
A communication error has occurred
in the internal data transmission.
Notify your author-
ised electrician.
E
Check the data
cable.
FS
35
Protect. shut-
down SW
Protection shutdown of the software
(AC overvoltage, AC overcurrent, DC
link overvoltage, DC overvoltage, DC
overtemperature).
Not a fault
Grid-related shutdown,
the grid connects again
automatically.
-
FS
36
Protect. shut-
down HW
Protection shutdown of the hardware
(AC overvoltage, AC overcurrent, DC
link overvoltage).
Not a fault
Grid-related shutdown,
the grid connects again
automatically.
-
FS
38
Generator over-
voltage error
The voltage of the DC generator is too
high. The PV generator is incorrectly
dimensioned.
Notify your author-
ised electrician.
E
FS
41
Line failure:
undervolt. L1
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Notify your author-
ised electrician.
E
FS
42
Line failure:
overvolt. L1
The voltage of a grid phase is too high,
the grid cannot be fed into.
The phase experiencing failure is dis-
played.
Notify your author-
ised electrician.
E
FS
43
Line failure:
undervolt. L2
The voltage of a grid phase is too low;
the grid cannot be fed into. The phase
experiencing failure is displayed.
Notify your author-
ised electrician.
E
Table 6:
Operating states and fault messages on the display
BS = operating status, FS = fault status;
B = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must be carried out only by a service employee of KACO new energy GmbH.