M a i n t e n a n c e / T r o u b l e s h o o t i n g

Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN

Page 45

Fault

Cause of fault

Explanation/remedy

By

The line fuse
trips.

The line fuse

capacity is too
low.

In cases of high irradiance, the inverter exceeds its rated cur-

rent for a short period, depending on the PV generator.

 Select the capacity of the inverter’s pre-fuse to be some-

what higher than the maximum feed-in current (see the
“Installation” section).

E

 Contact the grid operator if the grid failure constantly

occurs.

E

Damage to the

inverter’s hard-
ware.

If the line fuse trips immediately when the inverter goes into

feed-in mode (after the start-up period is complete), the invert-
er’s hardware is probably damaged.

 Contact KACO Service to test the hardware.

E

The inverter dis-
plays an impos-
sible daily peak
value.

Faults in the grid.

The inverter continues to operate as normal without losses to

the yield, even when an erroneous daily peak value is dis-
played. The value is reset overnight.

 To reset the value immediately, switch the inverter off by

disconnecting it from the grid and switching off the DC,
then switch it back on.

E

Daily yields do
not correspond to
the yields on the
feed-in meter.

Tolerances of

the measuring
elements in the
inverter.

The measuring elements of the inverter have been selected
to ensure maximum yields. Due to tolerances, the daily yields
shown may deviate from the values on the feed-in meter by
up to 15%.

 No action.

-

The inverter is
active but does
not feed into
the grid. Display:
“Waiting for
feed-in”

Generator volt-
age too low

Grid voltage or
PV generator
voltage unsta-
ble.

The PV generator voltage or power is not suffi

cient for feed-

in (solar irradiance is too low).

The inverter checks the line parameters before the feed-in
process begins. The length of the switch-on time diff ers by
country according to applicable standards and regulations
and can take several minutes.

The starting voltage may have been set incorrectly.

 Adjust starting voltage in the Parameter menu if required.

K

Table 5:

Troubleshooting

B = Action of the operator

E = The indicated work must only be carried out by an authorised electrician.

K = The indicated work must only be carried out by a service employee of KACO new energy GmbH.