Au es gb gr il it pt, Be bg cz fr de – KACO Powador 16.0 TR3 User Manual
Page 34

C o n f i g u r a t i o n a n d O p e r a t i o n
Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN
Page 35
Country-
spec. setting
Menu
level
Display/
Setting
Action in this menu/meaning
All countries
0
1
2
3
1
Web server
Activate or deactivate the integrated web server.
All countries
0
1
2
3
0
“Parameters”
menu
Press the right arrow button or the OK button.
NOTICE: The inverter does not display the “Parameters”
menu in the standard confi guration. To display the
menu:
1.
Open the menu.
2. Simultaneously hold down the up and down but-
tons for several seconds.
0
1
2
3
1
Country
1.
Input the four-character password via the 4-way
button. The password is unit-specifi c.
2. Confi rm the entry with the OK button.
3. Set the desired country setting.
NOTICE: This option infl uences the country-specifi c
operating settings of the inverter. Please consult KACO
service for further information.
0
1
2
3
1
Grid type/
guideline
Select the type of grid applicable to the use of the
inverter.
AU ES
GB GR
IL
IT
PT
0
1
2
3
1
Switch-off volt.
The inverter is equipped with redundant 3-phase moni-
toring. If the line voltage drops below the value set for
“Minimum line voltage”, the inverter switches off . The
minimum cut-off threshold can be set in 1 V increments.
Confi gure the switch-off values for undervoltage
and overvoltage.
BE
BG
CZ
FR
DE
NSp.
0
1
2
3
1
Grid shutd.
EN50160
The grid voltage is recorded and averaged over ten min-
utes. If the set value is exceeded, the inverter is discon-
nected from the grid.
Specify the voltage threshold.
BE
BG
CZ
FR
DE
NSp.
0
1
2
3
1
Voltage drop
The voltage drop between the inverter and the feed-in
meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can
be set from 0 to 11 V in 1 V increments.
Specify the switch-off value for the voltage drop
(0 to 11 V).
All countries
0
1
2
3
1
Switch-off freq.
The inverter monitors the line frequency continuously.
If the line frequency exceeds or drops below the confi g-
ured values, the inverter switches off .
Set limit values for underfrequency and overfre-
quency in 0.1 Hz steps.
0
1
2
3
1
DC starting volt.
The inverter begins feed-in as soon as this PV voltage is
present.
Set the starting voltage.