C o n f i g u r a t i o n a n d O p e r a t i o n

Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN

Page 35

Country-

spec. setting

Menu

level

Display/

Setting

Action in this menu/meaning

All countries

0

1

2

3

1

Web server

 Activate or deactivate the integrated web server.

All countries

0

1

2

3

0

“Parameters”

menu

 Press the right arrow button or the OK button.
NOTICE: The inverter does not display the “Parameters”
menu in the standard confi guration. To display the
menu:

1.

Open the menu.

2. Simultaneously hold down the up and down but-

tons for several seconds.

0

1

2

3

1

Country

1.

Input the four-character password via the 4-way
button. The password is unit-specifi c.

2. Confi rm the entry with the OK button.

3. Set the desired country setting.

NOTICE: This option infl uences the country-specifi c
operating settings of the inverter. Please consult KACO
service for further information.

0

1

2

3

1

Grid type/

guideline

 Select the type of grid applicable to the use of the

inverter.

AU ES
GB GR

IL

IT

PT

0

1

2

3

1

Switch-off volt.

The inverter is equipped with redundant 3-phase moni-

toring. If the line voltage drops below the value set for
“Minimum line voltage”, the inverter switches off . The
minimum cut-off threshold can be set in 1 V increments.

 Confi gure the switch-off values for undervoltage

and overvoltage.

BE

BG

CZ

FR

DE

NSp.

0

1

2

3

1

Grid shutd.

EN50160

The grid voltage is recorded and averaged over ten min-
utes. If the set value is exceeded, the inverter is discon-
nected from the grid.

 Specify the voltage threshold.

BE

BG

CZ

FR

DE

NSp.

0

1

2

3

1

Voltage drop

The voltage drop between the inverter and the feed-in

meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can
be set from 0 to 11 V in 1 V increments.

 Specify the switch-off value for the voltage drop

(0 to 11 V).

All countries

0

1

2

3

1

Switch-off freq.

The inverter monitors the line frequency continuously.

If the line frequency exceeds or drops below the confi g-
ured values, the inverter switches off .

 Set limit values for underfrequency and overfre-

quency in 0.1 Hz steps.

0

1

2

3

1

DC starting volt.

The inverter begins feed-in as soon as this PV voltage is

present.

 Set the starting voltage.