I n s t a l l i n g t h e I n v e r t e r

Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN

Page 25

Authorised electrician

Connecting the inverter with the network

↻ Connect the Ethernet cable to the inverter.

↻ Confi gure the Ethernet interface.

 Connect the Ethernet cable to the network or a computer.

 Confi gure the Ethernet settings and web server in the Settings menu (see section 8.3 on page 31).

7.3.2

Connecting the fault signal relay

The contact is designed as an N/O contact and is labelled “ERR” on the circuit board.

Maximum contact load:

DC: 30 V/1 A

AC: 250 V/1 A

Connecting the fault signal relay

1.

Unscrew the cable fi tting (see fi gure 10 on page 24).

2. Thread the connection cable through the cable fi tting.

3. Connect the connection cable to the socket.

4. Tighten the cable fi tting.

7.3.3

Connecting the 18 V output

An 18 V output is located on the communication board. It is used for supplying power to external sensors or similar
devices.

Connecting the 18 V output

1.

Unscrew the cable fi tting (see fi gure 10 on page 24).

2. Thread the connection cable through the cable fi tting.

3. Connect the connection cable to the connection terminals.

4. Tighten the cable fi tting.

7.3.4

Connecting the S0 output

An S0 pulse output is located on the communication board. Use this output to control accessories such as a large
display, for example. The pulse rate of the output is adjustable in the confi guration menu.

Connecting the S0 output

1.

Unscrew the cable fi tting (see fi gure 10 on page 24).

2. Thread the connection cable through the cable fi tting.

3. Connect the connection cable to the connection terminals.

4. Tighten the cable fi tting.