2 mechanical data – KACO Powador 16.0 TR3 User Manual
Page 13

T e c h n i c a l D a t a
Page 14
Operating Instructions Powador 16.0 TR3, 18.0 TR3_EN
4.2 Mechanical
data
16.0 TR3/18.0 TR3
Display
LCD graphical display, 3 LEDs
Controls
4-way key, 2 keys
Interfaces
Ethernet, USB, RS485, S0
Fault signal relay
Potential-free NO contact, max. 30 V DC/1 A or 250 V AC/1 A
AC connections: PCB terminal
PCB terminals inside the unit
(max. cross section: 6 mm² fl exible, 10 mm² rigid)
AC connections: Cable connection
Cable connection via M40 cable fi tting
DC connections: PCB terminal
PCB terminals inside the unit
(max. cross section: 10 mm² fl exible, 16 mm² rigid)
DC connections: Cable connection
Cable connection via M16 cable fi tting
Ethernet connection: Cable connection
Cable connection via M25 cable fi tting
Ambient temperature range [°C]
-25 to 60
Humidity range
(non-condensing) [%]
0 to 95
Maximum installation elevation
(m above sea level)
2,000
Temperature monitoring
Yes
Cooling (free convection (K)/fan (L))
L
Protection rating according to EN 60529
IP 54
Degree of contamination
PD2
Noise emission [dB(A)]
< 45/noiseless without fan operation
DC disconnect
Built-in
Housing
Cast aluminium
H x W x D [mm]
945 x 510 x 269
Total weight [kg]
Approx. 80
Table 2:
Mechanical data