Status
Display
Explanation
Action
FS
81,
82,
83
Protect. shutdown
line volt.
L1 L2, L3
Overvoltage has been detected on
a conductor. An internal protective
mechanism has disconnected the
device to protect it against damage.
In case of repeated
occurrence:
Notify your
authorised
electrician.
E
FS
84
Protect. shutdown
undervolt. DC link
A voltage deviation has been found
in the DC link. An internal protective
mechanism has disconnected the
device to protect it against damage.
In case of repeated
occurrence:
Notify your
authorised
electrician.
E
FS
85
Protect. shutdown
overvolt. DC link
E
FS
86
Protect. shutdown
DC link asymmetry
Overvoltage has been found in
the DC link. An internal protective
mechanism has disconnected the
device to protect it against damage.
In case of repeated
occurrence:
Notify your
authorised
electrician.
E
FS
87,
88,
89
Protection
shutdown
overcurrent L1, L2,
L3
A current that has been found
on a conductor is too high. An
internal protective mechanism has
disconnected the device to protect it
against damage.
In case of repeated
occurrence:
Notify your
authorised
electrician.
E
FS
93,
94
Buff er 1, buff er 2
self test error
The control board is defective.
Notify authorised
electrician / KACO
Service
E/K
FS
95,
96
Relay 1, relay 2 self
test error
The power section is defective.
Notify KACO
Service
K
FS
97
Protect. shutdown
overcurrent HW
Too much power has been fed into
the grid. Complete disconnection of
the device.
Notify authorised
electrician / KACO
Service
E/K
FS
98
Protect. shutdown
HW gate driver
An internal protective mechanism
has disconnected the device to
protect it against damage.
Complete disconnection of the
device.
Notify authorised
electrician / KACO
Service
E/K
FS
99
Protect. shutdown:
HW buff er free
An internal protective mechanism
has disconnected the device to
protect it against damage.
Complete disconnection of the
device.
Notify authorised
electrician / KACO
Service
E/K
FS
100
Protect. shutdown
HW overtemp.
The device has been switched off
because the temperatures in the
housing were too high.
Check to make sure
that the fans are
working.
Replace fan if
necessary.
B
E
Table 6: