I n s t a l l i n g t h e I n v e r t e r

Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD

Page 23

7.3.2.3 Standard 2 MPP PV system connection

Equal MPP voltages must be applied to input 1 and 2, as well as inputs 3 and 4. The MPP voltages of the two DC paths can
be diff erent. They are tracked by separate, independently operating MPP trackers (MPP trackers A and B). (n

1

=n

2

, n

3

=n

4

).

Electrical data for standard connection

Connection of the DC inputs

Number of modules per string n

1

=n

2

, n

3

=n

4

P

max

per string < 6 kW

MPP trackers A+B together < 12 kW

I

max

< 18.6 A per tracker

MPP tracker A

MPP tracker B

U

MPP

n

1

n

2

n

3

n

4

=

=

U

MPP

Figure 13: Recommended standard connection