KACO XP10U-H4 User Manual
Page 44
M a i n t e n a n c e / T r o u b l e s h o o t i n g
Page 44
Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD
Fault
Cause of fault
Explanation/remedy
By
Noise emission
from the inverter.
Particular ambient
conditions.
When there are certain ambient conditions, the units may emit
audible noises.
•
Line interference or grid failure caused by particular loads
(motors, machines, etc.) which are either connected to the
same point on the grid or located in the vicinity of the
inverter.
•
In cases of volatile weather conditions (frequent switching
between sunny and cloudy conditions) or strong irradiance,
a light hum may be audible due to the increased power.
•
Under particular grid conditions, resonances may form
between the unit’s input fi lter and the grid, which may be
audible even when the inverter is switched off .
These noise emissions do not aff ect the operation of the
inverter. They do not lead to loss of effi
ciency, failure, damage
or to a shortening of the unit’s service life.
People with very sensitive hearing (particularly children) are
able to hear the high-frequency hum caused by the inverter’s
operating frequency of approximately 17 kHz.
No action.
In spite of high
irradiance, the
inverter does
not feed in the
maximum power
into the grid.
The device is too
hot and the power
is reduced.
Because the temperatures inside the unit are too high, the
inverter reduces its power to prevent damage to the unit. Note
the technical data. Ensure unhindered convection cooling from
the exterior. Do not cover the cooling fi ns.
Provide for suffi
cient cooling of the unit.
Do not cover the cooling fi ns.
O, E
Table 5:
Troubleshooting
O = Action of the operator
E = The indicated work must only be carried out by an authorised electrician.
K = The indicated work must only be carried out by a service employee of KACO new energy, Inc.