5 messages on the display and the “fault” led, 1 display of status and fault messages, Status and fault signals – KACO XP10U-H4 User Manual
Page 45
M a i n t e n a n c e / T r o u b l e s h o o t i n g
Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD
Page 45
9.5
Messages on the display and the “Fault” LED
Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The minimum triggering
levels are determined by standards. The inverter must switch off if the permitted values are undershot or exceeded.
9.5.1
Display of status and fault messages
Display
Fault LED (red)
FS (fault status)
ON
•
Fault signal relay has switched.
•
Feed-in was ended due to a fault.
OS (operating status)
OFF
•
The fault signal relay deenergizes again.
•
The inverter feeds back into the grid again
after a country-specifi c time period.
On the display you can fi nd details regarding the fault or operating status or the data that was recorded through the
RS485 interface.
Status and fault signals
The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.
Status
Display
Explanation
Action
OS
1
Waiting for feed-in
Self-test: The grid parameters and
generator voltage are being checked.
-
-
OS
2
Generator voltage
too low
Insuffi
cient generator voltage and
power,
status before the transition to night
shutdown
-
-
OS
8
Self-test
Checks the shutdown of the power
electronics as well as the grid relay
before feed-in mode
-
-
FS
10
Temperature in
unit too high
In case of overheating, the inverter
switches off . Possible causes:
•
Ambient temperature too high
•
Fans covered
•
Inverter defect
Cool off the area
around the inverter.
Uncover the fans.
Notify your
authorised
electrician.
B
B
E
OS
11
Measured values
Power limitation: If the generator power is too high, the inverter
limits itself to the maximum power (e.g. around noon if the generator
capacity is too large).
FS
17
Shutting down
Powador-protect
The activated grid and system
protection has been tripped.
Wait for
reactivation.
Notify your
authorised
electrician if the
fault occurs several
times.
E
FS
18
Resid. current
shutdown
Residual current was detected. The
feed-in was interrupted.
Notify your
authorised
electrician.
E
Table 6:
Operating statuses and fault messages on the display