M a i n t e n a n c e / T r o u b l e s h o o t i n g

Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD

Page 45

9.5

Messages on the display and the “Fault” LED

Many fault signals indicate a fault in the grid. They are not operational faults of the inverter. The minimum triggering
levels are determined by standards. The inverter must switch off if the permitted values are undershot or exceeded.

9.5.1

Display of status and fault messages

Display

Fault LED (red)

FS (fault status)

ON

Fault signal relay has switched.

Feed-in was ended due to a fault.

OS (operating status)

OFF

The fault signal relay deenergizes again.

The inverter feeds back into the grid again
after a country-specifi c time period.

On the display you can fi nd details regarding the fault or operating status or the data that was recorded through the
RS485 interface.

Status and fault signals

The following table lists the possible status and fault signals that the inverter shows on the LCD and the LEDs.

Status

Display

Explanation

Action

OS

1

Waiting for feed-in

Self-test: The grid parameters and
generator voltage are being checked.

-

-

OS

2

Generator voltage
too low

Insuffi

cient generator voltage and

power,

status before the transition to night
shutdown

-

-

OS

8

Self-test

Checks the shutdown of the power
electronics as well as the grid relay
before feed-in mode

-

-

FS

10

Temperature in

unit too high

In case of overheating, the inverter
switches off . Possible causes:

Ambient temperature too high

Fans covered

Inverter defect

 Cool off the area

around the inverter.

 Uncover the fans.

 Notify your

authorised
electrician.

B

B
E

OS

11

Measured values

Power limitation: If the generator power is too high, the inverter
limits itself to the maximum power (e.g. around noon if the generator
capacity is too large).

FS

17

Shutting down
Powador-protect

The activated grid and system
protection has been tripped.

 Wait for

reactivation.

 Notify your

authorised
electrician if the
fault occurs several
times.

E

FS

18

Resid. current
shutdown

Residual current was detected. The
feed-in was interrupted.

 Notify your

authorised
electrician.

E

Table 6:

Operating statuses and fault messages on the display