KACO XP10U-H4 User Manual
Page 11
T e c h n i c a l D a t a X P 1 0 U H 4 / H 6 ( w i t h o p t i o n a l P S D )
Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD
Page 11
4
Technical Data XP10U H4 / H6 (with optional PSD)
Product
XP10U-H4
XP10U-H6 - PSD
DC electrical specifi cations 2 MPPT
DC maximum input voltage (VDC)
600
DC maximum peak power operating range (MPP)
(VDC)
280-550
DC operating range (VDC)
200-600*
DC minimum start voltage (VDC)
250
DC maximum operating current per
input A - B (ADC)
18.6
DC maximum short circuit current per
input A - B (ADC)
37
45
Max. backfeed current [A] (inverter to module)
0
DC input overload protection
Yes, Voltage and Current during operation
DC input terminals / conductor size
2 Pos and 2 Neg / 8-24 AWG
* The possible input power is reduced at voltages lower than 350 V. The input current is limited to 18.6 A per input.
AC electrical specifi cations
AC max continuous output power (W)
10.000
CEC weighted eff (%)
97,5
AC nominal voltage / operating range
L to Neutral (VAC)
480 / 243 to 304
600 / 305 to 381
AC continuous output current (A)
12.1
9.7
Frequency nominal / range (Hz)
60 / 60.5 to 59.3
Power factor
> .99
Total harmonic distortion %
< 5
Standbye losses (W)
< 1.5
AC short circuit protection
None
AC input terminals and conductor
4 / 4-18 AWG AL CU
AC Maximum output fault
current (A), RMS, and duration ms
625 A (P-P), 18.25 A (RMS ), 36.5ms
Utility Connection
Wye 4 wire (A,B,C,N)
** Maximum Output fault current and duration - 355A (P-P), 12.95A (RMS), 46.5 ms
PV system disconnect (Optional PSD)
Integrated AC / DC disconnect
Yes
AC and DC surge protection
Rotary switch visible and accesible from outside of enclosure
AC Disconnection ratings
20 A VAC Break L1-L2-L3
Table 1:
Electrical Data