KACO XP10U-H4 User Manual
Page 12
T e c h n i c a l D a t a X P 1 0 U H 4 / H 6 ( w i t h o p t i o n a l P S D )
Page 12
Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD
AC over current protection devices (OCPD)
Current limiting inverter, OCPD provided by system integrator
AC LOTO Provision
LOTO in OPEN
AC input terminals / conductor size
L1-L2-L3 / N (with optional PSD)
4 - 8 / 12 Awg
DC Disconnection means
Rotary switch accesible from inside of enclosure with no
tools required
DC Disconnection ratings
20 A, 4 pole, Load Break, Pos and Neg
DC over current protection devices (OCPD)
Current limiting inverter, OCPD provided by system integrator
DC LOTO Provision
LOTO in OPEN
DC input terminals / conductor size, per channel
(with optional PSD)
2 Pos and 2 Neg / 6 -14 AWG
Mechanical and environmental specifi cations
Mechanical integration
Ground mount, Roof Mount
Enclosure construction
Cast Al for XP10U, Power coated steel for PSD.
Unit Weight (lb/kg)
Inv and Inv with PSD
88 /40
100 / 45
Unit dimensions HxWxD (In/mm)
(37 x 16.5 x 7.9 / 940 x 420 x 200)
(27.2 x 16.5 x 7.9 / 690 x 420 x 200)
Environmental
Operating temp range (°F / °C)
(-13 to 140 / -25 to 60)
Storage temp range (°F / °C)
(-22 to 158 / -30 to 70)
Noise emissions
< 55 db
Humidity %
0 to 95 non condensing
Enclosure rating Inverter / PV system disconnect
NEMA 4
Cooling
Forced convection with variable speed fan
Altitude (ft / m)
6500 / 2000
Communications and user interface
User interface
Graphical user interface with 3 LED status indicators
Connectivity
(Ethernet / USB / RS485 / S0 output)
Safety features and regulatory compliance
UL / IEEE / CSA / FCC
UL 1741x 2nd Ed 2010 / CSA C22.2No 107.1 / IEEE 1547 /
FCC Class B /
Fault signal relay
Potential free normally open contact
DC polarity safegaud
Short circuit diode
GFDI compliant with NEC 690.35 for use with
ungrounded PV system arrays.
UL1741 listed for residual ground fault current isolation
monitor and interrupter function.
Table 1:
Electrical Data