4.1
Trip Ievel settings to shutdown Inverter
No. Description
Trip setting
Persistant time
1
DC Input Over Voltage Level 1
550 V_DC
2 sec
2
DC Input Over Voltage Level 2
600 V_DC
20 msec
3
DC Input Under Voltage
200 V_DC
1 sec
4
DC Input Over Current (SW)
23 A_DC
100 μsec
5
DC Input Instantaneous Over Current (HW)
35 A_DC
2 μsec
6
DC Link Instantaneous Over Voltage
1050 V_DC
200 μsec
7
DC Link Instantaneous Under Voltage
825 V_DC
1 msec
8
Inverter Over Current
21 A_peak
100 μsec
9
Inverter Instantaneous Over Current
25 A_peak
2 μsec
Table 2:
Trip level settings to shutdown Inverter
4.2
Trip Ievel settings to stop Inverter
Description
Minimum
level
Maximum
level
Default
level
Minimum
time
Maximum
time
Default
time
Line Under Voltage Fast
50 %
88 %
50 %
0.16 sec
0.16 sec
0.16 sec
Line Under Voltage Slow
50 %
100 %
88 %
0.16 sec
2 sec
2 sec
Line Over Voltage Fast
110 %
110 %
110 %
0.16 sec
0.16 sec
0.16 sec
Line Over Voltage Slow
100 %
110 %
110%
0.16 sec
1 sec
0.16 sec
Line Under Frequency Level 1
57 Hz
59.8 Hz
59.3 Hz
0.16 sec
300 sec
0.16 sec
Line Under Frequency Level 2
57 Hz
57 Hz
57 Hz
0.16 sec
0.16 sec
0.16 sec
Line Over Frequency
60 Hz
60.5 Hz
60.5 Hz
0.16 sec
0.16 sec
0.16 sec
Table 3:
Trip level settings to stop Inverter