T e c h n i c a l D a t a X P 1 0 U H 4 / H 6 ( w i t h o p t i o n a l P S D )

Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD

Page 13

4.1

Trip Ievel settings to shutdown Inverter

No. Description

Trip setting

Persistant time

1

DC Input Over Voltage Level 1

550 V_DC

2 sec

2

DC Input Over Voltage Level 2

600 V_DC

20 msec

3

DC Input Under Voltage

200 V_DC

1 sec

4

DC Input Over Current (SW)

23 A_DC

100 μsec

5

DC Input Instantaneous Over Current (HW)

35 A_DC

2 μsec

6

DC Link Instantaneous Over Voltage

1050 V_DC

200 μsec

7

DC Link Instantaneous Under Voltage

825 V_DC

1 msec

8

Inverter Over Current

21 A_peak

100 μsec

9

Inverter Instantaneous Over Current

25 A_peak

2 μsec

Table 2:

Trip level settings to shutdown Inverter

4.2

Trip Ievel settings to stop Inverter

Description

Minimum

level

Maximum

level

Default

level

Minimum

time

Maximum

time

Default

time

Line Under Voltage Fast

50 %

88 %

50 %

0.16 sec

0.16 sec

0.16 sec

Line Under Voltage Slow

50 %

100 %

88 %

0.16 sec

2 sec

2 sec

Line Over Voltage Fast

110 %

110 %

110 %

0.16 sec

0.16 sec

0.16 sec

Line Over Voltage Slow

100 %

110 %

110%

0.16 sec

1 sec

0.16 sec

Line Under Frequency Level 1

57 Hz

59.8 Hz

59.3 Hz

0.16 sec

300 sec

0.16 sec

Line Under Frequency Level 2

57 Hz

57 Hz

57 Hz

0.16 sec

0.16 sec

0.16 sec

Line Over Frequency

60 Hz

60.5 Hz

60.5 Hz

0.16 sec

0.16 sec

0.16 sec

Table 3:

Trip level settings to stop Inverter