KACO XP10U-H4 User Manual
Page 46
M a i n t e n a n c e / T r o u b l e s h o o t i n g
Page 46
Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD
Status
Display
Explanation
Action
FS
19
Generator
insulation fault
There is an insulation fault on the
PV generator. The feed-in was
interrupted.
Notify your
authorised
electrician if the
fault occurs several
times.
E
FS
30
Instrument
transformer fault
The current and voltage
measurements in the inverter are not
plausible.
-
-
FS
32
Fault
Self-test
The internal grid separation relay test
has failed.
Notify your
authorised
electrician if the
fault occurs several
times.
E
FS
33
Fault
DC feed-in
The DC feed-in has exceeded the
permitted value. This DC feed-in can
be adopted from the grid onto the
inverter so that no fault occurs.
Notify your
authorised
electrician if the
fault occurs several
times.
E
FS
34
Internal
communication
error
A communication error has occurred
in the internal data transmission.
Notify your
authorised
electrician.
E
Check the data
cable.
FS
35
Protect. shutdown
SW
Protective shutdown of the
software (AC overvoltage, AC
overcurrent, DC link overvoltage, DC
overvoltage, DC overtemperature).
Not a fault Grid-related
shutdown, the grid connects
again automatically.
FS
36
Protect. shutdown
HW
Protective shutdown of the
hardware (AC overvoltage, AC
overcurrent, DC link overvoltage).
Not a fault Grid-related
shutdown, the grid connects
again automatically.
FS
38
Generator
overvoltage error
The voltage of the DC generator
is too high. The PV generator is
confi gured incorrectly.
Notify your
authorised
electrician.
E
FS
41
42
Line failure:
Under voltage L1,
Over voltage L1
The voltage of a grid phase is too low
or high; the grid cannot be fed into.
The phase experiencing failure is
displayed.
Notify your
authorised
electrician.
E
43
44
Under voltage L2,
Over voltage L2
45
46
Under voltage L3,
Over voltage L3
FS
47
Line failure: line-to-
line voltage
The measured line-to-line voltage is
outside of the tolerance limits.
FS
48
Line failure:
Under frequency
Grid frequency is too low.
This fault may be grid-related.
Notify your
authorised
electrician.
E
Table 6:
Operating statuses and fault messages on the display