M a i n t e n a n c e / T r o u b l e s h o o t i n g

Page 46

Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD

Status

Display

Explanation

Action

FS

19

Generator
insulation fault

There is an insulation fault on the
PV generator. The feed-in was
interrupted.

 Notify your

authorised
electrician if the
fault occurs several
times.

E

FS

30

Instrument

transformer fault

The current and voltage
measurements in the inverter are not
plausible.

-

-

FS

32

Fault

Self-test

The internal grid separation relay test
has failed.

 Notify your

authorised
electrician if the
fault occurs several
times.

E

FS

33

Fault

DC feed-in

The DC feed-in has exceeded the
permitted value. This DC feed-in can
be adopted from the grid onto the
inverter so that no fault occurs.

 Notify your

authorised
electrician if the
fault occurs several
times.

E

FS

34

Internal
communication
error

A communication error has occurred
in the internal data transmission.

 Notify your

authorised
electrician.

E

 Check the data

cable.

FS

35

Protect. shutdown
SW

Protective shutdown of the
software (AC overvoltage, AC
overcurrent, DC link overvoltage, DC
overvoltage, DC overtemperature).

Not a fault Grid-related
shutdown, the grid connects
again automatically.

FS

36

Protect. shutdown
HW

Protective shutdown of the
hardware (AC overvoltage, AC
overcurrent, DC link overvoltage).

Not a fault Grid-related
shutdown, the grid connects
again automatically.

FS

38

Generator
overvoltage error

The voltage of the DC generator
is too high. The PV generator is
confi gured incorrectly.

 Notify your

authorised
electrician.

E

FS

41
42

Line failure:

Under voltage L1,
Over voltage L1

The voltage of a grid phase is too low
or high; the grid cannot be fed into.
The phase experiencing failure is
displayed.

 Notify your

authorised
electrician.

E

43

44

Under voltage L2,
Over voltage L2

45

46

Under voltage L3,
Over voltage L3

FS

47

Line failure: line-to-
line voltage

The measured line-to-line voltage is
outside of the tolerance limits.

FS

48

Line failure:

Under frequency

Grid frequency is too low.
This fault may be grid-related.

 Notify your

authorised
electrician.

E

Table 6:

Operating statuses and fault messages on the display