M a i n t e n a n c e / T r o u b l e s h o o t i n g

Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD

Page 47

Status

Display

Explanation

Action

FS

49

Line failure:

Over frequency

Grid frequency is too high.
This fault may be grid-related.

 Notify your

authorised
electrician.

E

FS

50

Line failure:

average voltage

The grid voltage measurement
according to EN 50160 has exceeded
the maximum permitted limit value.
This fault may be grid-related.

 Notify your

authorised
electrician.

E

FS

57

Waiting for

reactivation

Waiting time of the inverter after a
fault.

Inverter does not switch
on again until the country-
specifi c time has elapsed.

FS

58

Control board

overtemperature

The temperature inside the unit was
too high. The inverter switches off to
prevent damage to the hardware.

 Provide for

suffi

cient

ventilation.

E

FS

59

Self test error

A fault occurred during a self-test.

 Notify your

authorised
electrician.

E

OS

60

Generator voltage
too high

The inverter does not begin feeding
into the grid until the PV voltage falls
below a specifi ed value.

-

-

OS

61

External
limit (%)

The external limit Power control was activated by the grid operator.
The inverter limits its power.

OS

63

Measured values

P(f)/frequency-dependent power reduction: Frequency-dependent
power reduction will be activated when the BDEW (German
Association of Energy and Water Industries) Medium Voltage Directive
goes into eff ect. Power reduction starts at a frequency of 50.2 Hz.

OS

64

Measured values

Output current limiting: The AC current is limited once the specifi ed
maximum value has been reached.

FS

67

Fault at power
section 1

There is a fault in the power section.

 Notify your

authorised
electrician.

E

FS

70

Fan error

Fan 1 is malfunctioning.

 Replace

defective fan

E

FS

73

Standalone grid err.

Standalone mode was detected.

-

-

OS

74

External idle power
requirement

The grid operator limits the feed-in
power of the inverter.

-

-

OS

79

Insulation
measurement

PV generator’s insulation is being
measured

-

-

FS

80

Insulation meas.
not possible

The insulation measurement cannot
be performed because the generator
voltage is too volatile.

-

-

Table 6:

Operating statuses and fault messages on the display