I n s t a l l i n g t h e I n v e r t e r
Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD
Page 19
7.2.2
Accessing the XP10U H4 / H6 PSD inverter AC and DC circuit connections
CAUTION
Risk of damaging cable and components.
Drilling AC-/DC-knock-outs in NEMA 4 PSD box can damaging cable and existing components.
›
Carefully drill accessing knock-outs according area in drawing.
›
Use UL 514B watertight conduit connections at the conduit entrances.
In order to avoid interference between current-carrying leads and interface cables, adhere to the following drawings:
3,96
100,57
2,00
50,80
3,00 76,20
0,50 12,70
1,00
25,40
1,00 25,40
0,50
12,70
3,00
76,20
2,00 50,80
1,38 34,93
3,00
76,20
1,85
46,94
0,50 12,70
Figure 11: shows the recommended placement, and the trade size K.O’s
Bore AC-/DC-knock-outs
↻ Defi ne AC/DC-knock-outs area according above drawing.
1.
Mark position on the PSD box.
2. Bore AC-/DC-knock-outs with suitable drill.
3. Deburr
knock-outs.
4. Remove careful all dirt and chips in the housing.
5. Insert UL 514B watertight conduit connections at the conduit entrances.
»
Make electrical connection.