I n s t a l l i n g t h e I n v e r t e r

Installation Instructions blueplanet XP10U H4 / H6 and XP10U H4 / H6 PSD

Page 19

7.2.2

Accessing the XP10U H4 / H6 PSD inverter AC and DC circuit connections

CAUTION

Risk of damaging cable and components.

Drilling AC-/DC-knock-outs in NEMA 4 PSD box can damaging cable and existing components.

Carefully drill accessing knock-outs according area in drawing.

Use UL 514B watertight conduit connections at the conduit entrances.

In order to avoid interference between current-carrying leads and interface cables, adhere to the following drawings:

3,96

100,57

2,00

50,80

3,00 76,20

0,50 12,70

1,00

25,40

1,00 25,40

0,50

12,70

3,00

76,20

2,00 50,80

1,38 34,93

3,00

76,20

1,85

46,94

0,50 12,70

Figure 11: shows the recommended placement, and the trade size K.O’s

Bore AC-/DC-knock-outs

↻ Defi ne AC/DC-knock-outs area according above drawing.
1.

Mark position on the PSD box.

2. Bore AC-/DC-knock-outs with suitable drill.

3. Deburr

knock-outs.

4. Remove careful all dirt and chips in the housing.

5. Insert UL 514B watertight conduit connections at the conduit entrances.

»

Make electrical connection.