Maintenance/Troubleshooting

Page 50

Operating Instructions for KACO blueplanet 3.0-4.6 TL1

Status

Display

Explanation

Action

FS

33

Fault

DC feed-in

The DC feed-in has exceeded the

permitted value. This DC feed-in can
be caused by grid conditions and
may not necessarily indicate a fault.

 Notify your author-

ised electrician if the
fault occurs several
times.

E

FS

35

Protection shut-

down SW

Protective shutdown of the

software (AC overvoltage, AC over-
current, DC link overvoltage, DC
overvoltage, DC overtemperature).

Not a fault Grid-related

shutdown, the grid connects
again automatically.

FS

37

Unknown

hardware

Device does not detect expansion

hardware.

 Additional hardware

faulty or not original
KACO accessories!

B

FS

38

Generator overvolt-

age error

The voltage of the DC generator is

too high. The PV generator is confi g-
ured incorrectly.

 Notify your author-

ised electrician.

E

FS

41

42

Line failure:

Under voltage L1,

Over voltage L1,

The voltage of a grid phase is too

low; the grid cannot be fed into. The
phase experiencing failure is dis-
played.

 Notify your author-

ised electrician.

E

43

44

Under voltage L2,

Over voltage L2,

45

46

Under voltage L3,

Over voltage L3,

FS

47

Grid failure phase-

to-phase voltage

The measured line-to-line voltage is

outside of the tolerance limits.

 Notify your author-

ised electrician.

E

FS

48

Line failure:

Underfrequency

Grid frequency is too low.

This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

49

Line failure:

Overfrequency

Grid frequency is too high.

This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

50

Line failure:

average voltage

The grid voltage measurement

according to EN 50160 has exceeded
the maximum permitted limit value.
This fault may be grid-related.

 Notify your author-

ised electrician.

E

FS

51

53

Grid failure:

average voltage L1
/ L2

String voltage L1 / L2 is above the

set maximum permissible string
voltage

 Notify your author-

ised electrician.

E

FS

52

54

Grid failure:

mid-undervoltage
L1 / L2

String voltage L1 / L2 is below the

set maximum permissible string
voltage

 Notify your author-

ised electrician.

E

FS

57

Waiting for

reactivation

Waiting time of the inverter after a

fault.

Inverter does not switch on

again until the country-specifi c
time has elapsed.

Table 4:

Operating status and fault messages on the display