2 dc plug connector – KACO blueplanet 3.0 - 4.6 TL1 User Manual
Page 20
EN
EN
Installation
Page 20
Operating Instructions for KACO blueplanet 3.0-4.6 TL1
Authorised electrician
Recommended conductor
cross-section
Protection
2.5 - 6.0 mm²
25 A for 4.0 mm² conductor cross-section
Table 3:
Recommended conductor cross-section
Select conductor cross-section, safety type and safety value in accordance with the following master condi-
tions:
- Country specifi c installation standards
- Power rating of the device
- Line length
- Type of line installation
- Local temperatures
7.2.2
DC plug connector
5
1
2
6
4
3
1
2
15
4
3
7
Figure 18: Insert wires
Figure 19: Slide insert into sleeve
Figure 20: Check fastening
Key
1
Wires for DC connection
4
Sleeve
6
Contact plug
2
Spring
5
cable fi tting
7
Coupling
3
Insert
6
Contact plug
Confi guring the DC connector
NOTE: Before proceeding with the isolation ensure that you don't cut any individual wires.
1.
Isolate wires for DC connection by 15 mm.
2. Insert isolated wires with twisted ends carefully up to the end stop.
NOTE: Wire ends must be visible in the spring.
3. Close the spring so that the spring latches.
4. Slide insert into sleeve.
5. Tighten cable fi tting with the help of a 15" fork wrench applying a torque of 2 Nm.
6. Join insert with contact plug.
7. Check latch by lightly pulling on the coupling.
»
Make the electrical connections.
NOTE
The permissible bending radius of at least 4x the cable diameter should be observed during installa-
tion. Excessive bending force may negatively impact the protection rating.
All mechanical loads must be absorbed in front of the plug connection.