EN

Configuration and Operation

Operating Instructions for KACO blueplanet 3.0-4.6 TL1

Page 37

Coun-

try-spec.

setting

menu

level

Display/

setting

Action in this menu/meaning

GB, IL, IT, AT,

UD

0

1

2

3

1

Overvoltage shutd.

 Specify the shutdown threshold

for fast and slow overvoltage shutdown.

 Set period from occurrence of the fault to shutdown

of the inverter.

GB, IL, IT, AT,

UD

0

1

2

3

1

Undervoltage

shutd.

 Specify the shutdown threshold

for fast and slow undervoltage shutdown.

 Set period from occurrence of the fault to shutdown

of the inverter.

FR, UD

0

1

2

3

1

Voltage drop

The voltage drop between the inverter and the feed-in

meter is added to the limit value that was set for grid
shutdown according to EN 50160. The limit value can be
set from 0 to 11 V in 1 V increments.

 Specify the switch-off value for the voltage drop (0

to 11 V).

GB59/3, IT, IL,

AT, UD

0

1

2

3

1

Overfreq. shutd.

 Set limit value for overfrequency shutdown.

0

1

2

3

1

Underfreq. shutd.

 Set limit value for the underfrequency shutdown.

IL, IT, AT, UD

0

1

2

3

1

Activation

condition

The inverter checks mains voltage and frequency. The
grid feed operation begins if the measured values are
within the set ranges.

 Set minimum and maximum values for the switch-

ing on.

DE, BE, GB, IL,

IT, JO, AT, CY,

UD

0

1

2

3

1

Connect time

 Set period for grid observation (in seconds) when

switching on and reconnection after a fault.

ZA, UD

0

1

2

3

1

Power reduction

P(f)

 Activates the power reduction with selection of an

operating mode P(f )

 For selected mode OFF, 1 or 2

enter P(f ) thresholds and gradient.

IL, IT, UD

0

1

2

3

1

P(f) Gradient

 Set gradient of power limit function with increasing

frequency in % / Hz. This percentage relates to the
nominal frequency of 50 Hz

0

1

2

3

1

P(f) thresholds

 Set the frequency thresholds for activating and

deactivating the power limitation in Hz.

DE, CH, AU,

BE, FR, GB,

GR, IL, IT, JO,

NL, AT, CY,

UD, TW

0

1

2

3

1

DC starting volt.

The inverter begins feed-in as soon as this DC voltage is

present.

 Set the starting voltage.