Configuration and Operation

Page 36

Operating Instructions for KACO blueplanet 3.0-4.6 TL1

Coun-

try-spec.

setting

menu

level

Display/

setting

Action in this menu/meaning

0

1

2

3

1

Country

1.

Enter the four-digit password using the 4-way
button. The password is unit-specifi c.

2. Confi rm the entry with the OK button.

3. Set the desired country setting.

NOTE: This option infl uences the country-specifi c
operating settings of the inverter. Please consult KACO
service for further information.

DE, CH, FR,

GB GR, IT

0

1

2

3

1

Grid type/guide-

line

 Select the grid type for the inverter’s installation

location.

IT

Activate

self-test

It is only possible to activate the self-test in feed-in

mode.

The voltage and frequency dependent shutdown limits

are checked in the process.

AT, AU, BE,

DE, CH, FR ,

GB, GR, IT, IL,

JO, NL, UD,

CY, TW

0

1

2

3

1

Grid monitoring

Off ers the option of activating or deactivating three-

phase grid monitoring.

 Switching the grid monitoring on or off .

AT, GB, JO

0

1

2

3

1

Protection param-

eters

Display of 2-phase protection parameters.

 To show the protection parameters, select the “Dis-

play” key.

AU, GR, NL

0

1

2

3

1

Switch-off volt.

The inverter is equipped with redundant 3-phase moni-

toring. If the grid frequency exceeds or drops below the
confi gured values, the inverter switches off . The mini-
mum switch-off threshold can be set in 1 V increments.

 Confi gure the switch-off values for undervoltage

and overvoltage.

 Where necessary, set period from occurrence of the

fault to shutdown of the inverter.

AU, FR, GR, IL

0

1

2

3

1

Switch-off freq.

The inverter continuously monitors the grid frequency. If

the grid frequency exceeds or drops below the confi g-
ured values, the inverter switches off .

 Set limit values for underfrequency

and overfrequency in 0.1 Hz increments.

 Set period from occurrence of the fault to shutdown

of the inverter.

DE, CH, BE,

FR, IT, AT, CY,

UD

0

1

2

3

1

Overvoltage shutd.

 Activate or deactivate password protection.

(optional)

 Specify the shutdown threshold

for overvoltage shutdown.
The 10-minute average for the measured voltage as
per EN50160 is used.

 Set period from occurrence of the fault to shutdown

of the inverter.