Configuration and Operation

Page 38

Operating Instructions for KACO blueplanet 3.0-4.6 TL1

Coun-

try-spec.

setting

menu

level

Display/

setting

Action in this menu/meaning

DE, CH, AU,

BE, FR, GB,

GR, IL, IT, JO,

NL, AT, CY,

UD, TW

0

1

2

3

1

Const. volt. ctrl.

Lets you deactivate the MPP seek mode in order to oper-
ate the inverter with a constant DC voltage.

 Activate or deactivate function.

 Set value for constant voltage control (125 - 510 V).

NOTE: For voltages below the minimal MPP voltage the

possible input power is reduced. The input current is
limited here to 11A per input.

DE, CH, AU,

BE, FR, GB,

GR, IL, IT, JO,

NL, AT, CY,

UD, TW

0

1

2

3

1

Power

limitation

The output power of the inverter can be set perma-
nently to a lower value than the maximum output
power by the internal power limiting. This may be nec-
essary in order to limit the maximum power rating of
the system at the grid connection point, upon the grid
operator's request.

The value can be protected from the very fi rst output
limitation entry. After setting a limitation, the value can
only be changed by entering a device-specifi c password.

1.

Activate password protection if necessary.

2. Specify the activation status.

3. Specify the limit value for maximum feed-in power.

4. Confi rm the entry with the OK button.

DE, CH, AU,

BE, FR, GB,

GR, IL, IT, JO,

NL, AT, CY,

UD, TW

0

1

2

3

1

Powador-protect

Confi gures the support for grid shutdown by a Powador
protect connected to the digital input of the inverter.

↻ For Auto/On: A Powador protect is operating in

the photovoltaic system and is connected to the
inverter at the digital input/output.

 Auto: The inverter automatically detects a Pow-

ador-protect integrated into the photovoltaic
system.

 On: The digital signal of the Powador protect must

be present to the digital input of the inverter for the
inverter to start with feed-in.

 Off : The inverter does not check whether a Pow-

ador-protect is integrated into the PV system.

DE, CH, AU,

BE, FR, GB,

GR, IL, IT, JO,

NL, AT, CY, UD

0

1

2

3

1

Iso.resistor

 Set threshold value (in 1 kOhm steps) at which the

insulation monitor reports a fault.