Product: KACO blueplanet

4.0 TL1

4.6 TL1

5.0 TL1**

Input levels

DC MPP range from [V] to [V]

185 ... 510

215 ... 510

235 ... 510

Operating range from [V] to [V]

125 ... 550

Starting voltage [V]*

150

No-load voltage (U

OC max

) [V]

600 (start to 550)

Max. input current [A]

2 x 11

Max. power per tracker [W]

4100

4700

5140

Number of strings

2

Number of MPP controls

2

Max. short-circuit current [A]

25

Polarity safeguard

Short-circuit diode

Overvoltage category

III

Output levels

Rated power [VA]

4000

4600

5000

Grid voltage [V]

230 (1/N/PE)

Rated current [A]

17.5

20.0

21.7

Max. rated current [A]

19.5

22.0

22.0

Rated frequency [Hz]

50

cos phi

0.30 inductive ... 0.30 capacitive

Number of feed-in phases

1

Distortion factor [%]

0.79

0.79

Overvoltage category

III

General electrical data

Max. effi

ciency [%]

97.2

97.2

97.2

European effi

ciency [%]

96.6

96.6

96.6

Make current [A] and ON duration [ms]

1.82

Internal consumption: night [W]

3

Feed-in starts at [W]

20

Circuit design

Transformerless

Grid monitoring

Country-specifi c

Ground fault monitoring

Yes

Table 1:

Electrical data

* The DC starting voltage can be in the menu if needed.

** use permitted, except DE, CH, AT and DK