EN

Configuration and Operation

Operating Instructions for KACO blueplanet 3.0-4.6 TL1

Page 39

Coun-

try-spec.

setting

menu

level

Display/

setting

Action in this menu/meaning

DE, CH, BE,

GB, IL, IT, JO,

AT, CY, UD

0

1

2

3

1

Reactive power

 Open the menu: Press the right arrow button or the

OK button.

 Activating idle power process: select process and

press OK. The active process is highlighted.

0

1

2

3

2

cos-phi specifi ca-

tion

 Confi gure power factor.

 If a power factor is selected which is not equal to

1: Select the type of phase shift (under-excited/
over-excited).

DE, CH, BE,

GB, IL, IT, JO,

AT, CY, UD

0

1

2

3

2

cos-phi(P/Pn)

 Open the menu: Press the right arrow button or the

OK button.

GB, IL, IT, PL,

JO, AT, UD

0

1

2

3

2

Q const.

 Set the idle power Q (in %) to a fi xed value.

 Select the type of phase shift (under-excited/

over-excited).

CH, GB, IT, JO,

CY

0

1

2

3

3

Lock-in voltage

 Voltage range set as % of rated voltage, where the

network support process is active.

0

1

2

3

3

Lock-out

voltage

DE, CH, BE,

GB, PL, IL, IT,

JO, AT, CY, UD

0

1

2

3

3

Number of

nodes

This option defi nes how many support points can be
defi ned in the subsequent menu. The maximum number
of confi gurable support points depends on the selected
grid type.

 Specify the number of support points for the idle

power characteristic curve.

0

1

2

3

3

1., 2. ...Support

point

 Specify the power factor for the 1st, 2nd (etc.) sup-

port point

 If a power factor is selected which is not equal to

0: Select the type of phase shift (under-excited/
over-excited).

CH, GB, IT, PL

JO, AT, UD

0

1

2

3

2

Q(U) 5 Supports

 Open the menu: Press the right arrow button or the

OK button.

0

1

2

3

3

Lock-in power

 Power range set as % of rated power, in which the

network support process is active.

0

1

2

3

3

Lock-out power

0

1

2

3

3

Time constant

 Set the response speed of the control.

0

1

2

3

3

Number of

nodes

 Specify the number of support points for the idle

power characteristic curve.

0

1

2

3

3

1., 2. ...Support

point

 Specify the support points for voltage, power and

nature of the phase shift