beautypg.com

1 connect pv generator to device, 2 before connecting – KACO blueplanet 3.0 - 4.6 TL1 User Manual

Page 22

background image

EN

EN

Installation

Page 22

Operating Instructions for KACO blueplanet 3.0-4.6 TL1

Authorised electrician

7.4.1

Connect PV generator to device

DANGER

Risk of fatal injury due to contact voltage!

In accordance with IEC62109-1 §5.3.1., grounding on the PV modules or strings is prohibited under
any circumstances.

NOTE

In accordance with IEC 61730 Class A, connected PV modules must be dimensioned
for the DC system voltage provided, and at least for the value of the AC grid voltage.

DANGER

Risk of fatal injury due to contact voltages.

During installation: Electrically disconnect the DC positive and DC negative from the protective
earth (PE).

Disconnect the inverter from the PV generator using the integrated DC isolator switch.

Remove the plug connector.

1

2

A

B

Figure 23: Connections for DC positive and DC negative

Key

A

MPP tracker A

B

MPP tracker B

1

DC plus/DC minus connection

2

DC plus/DC minus connection

7.4.2 Before

connecting

Ensure that there is no ground fault

1.

Determine the DC voltage and resistance on the PV generator for:

protective earth (PE) and positive cable

protective earth (PE) and negative cable

If stable voltages can be measured, there is a ground fault in the DC generator or its wiring. The ratio between the
measured voltages gives an indication as to the location of this fault.

In addition, ensure that the PV generator has a total insulation resistance of more than 2.0 MOhm, since the
inverter will not feed in if the insulation resistance is too low.

2. Rectify any faults before connecting the DC generator.

Connect the PV generator to the DC positive and the DC negative connection plugs on the underside of the housing
(see Figure 23).