beautypg.com

SMA SMC 7000HV Installation User Manual

Page 81

background image

SMA Solar Technology AG

Technical Data

Installation Manual

SMC70HV11-IA-IEN112970

81

Protective devices

General Data

DC reverse-polarity protection

Short circuit diode

Input-side disconnection device

Electronic Solar Switch

DC overvoltage protection

thermally monitored varistors

AC short-circuit current capability

Current control

Grid Monitoring

SMA Grid Guard 2.1

Maximum permissible fuse protection

50 A

Ground fault monitoring

Insulation monitoring: R

iso

> 1 M Ω

Galvanic isolation

Available

Width x Height x Depth with
Electronic Solar Switch

468 mm x 653 mm x 242 mm

Weight

65 kg

Length x width x height of packaging

396 mm x 803 mm x 596 mm

Transport weight

68 kg

Climatic category according to IEC 60721-2-1

4K4H

Operation temperature range

‒25°C … +60°C

Maximum permissible value for relative humidity,
non-condensing

100%

Maximum operating altitude above mean sea
level

2 000 m

Noise emission (typical)

≤ 41 dB(A)

Power loss in night operation

0.25 W

Topology

LF transformer

Cooling concept

OptiCool: temperature-controlled fan

Fan connection

designed for safe disconnection in accordance

with DIN EN 50178:1998-04

Degree of protection for electrics according to
IEC 60529

IP65

Protection class (according to IEC 62103)

I